Eaton PXK-D16/1N/003-F - Residual current circuit breaker - F-type - 10000 A - IP20
Only 1 piece in stock at third-party supplier
Product details
Eaton RCD/LS combination PXK-D16/1N/003-F
Manufacturer: Eaton
Designation: RCD/LS combination 16 A, 30 mA, D
Type: PXK-D16/1N/003-F
Number of poles (total): 2
Number of fused poles: 1
Rated voltage: 240 V
Rated insulation voltage Ui: 440 V
Rated impulse withstand voltage Uimp: 4 kV
Rated current: 16 A
Rated residual current: 0.03 A
Residual current type: A
Energy limitation class: 3
Rated breaking capacity according to EN 61009: 10 kA
Rated breaking capacity according to IEC 60947-2: 0 kA
Rated breaking capacity Icn according to EN 61009-1: 10 kA
Tripping characteristic: instantaneous
Surge current withstand: 3 kA
Voltage type: AC
Frequency: 50 Hz
Tripping characteristic: D
Switching neutral: yes
With interlocking device: no
Overvoltage category: 3
Pollution degree: 2
Ambient temperature during operation: -25 to 40 °C
Width in pitch units: 2
Installation depth: 75.5 mm
Flush mounting: no
False tripping protection: yes
Protection class (IP): IP20
Connectable conductor cross-section solid: 1 to 25 mm²
Connectable conductor cross-section stranded: 1 to 25 mm²
Eaton FI/LS combination PXK-D16/1N/003-F: further details
High-quality residual current circuit-breaker/line circuit-breaker combination, mains-voltage-independent, contact position indicator red-green, terminal backsplash protection, tristable latching slide - enables removal from an existing busbar system, extensive range of accessories for retrofitting, large selection of rated residual currents, rated currents up to 40 A, tripping characteristics B, C, D, rated breaking capacity 10 kA, suitable for outdoor use (construction and outdoor distribution boards) down to -25 °C.
Circuit breaker type | Miniature circuit-breaker/residual current circuit-breaker combination |
Mounting type | Flush-mounted |
number of poles | 2 |
Item number | 31984006 |
Manufacturer | Eaton |
Category | Residual-current device |
Manufacturer No. | 193534 |
Release date | 24.10.2022 |
Circuit breaker type | Miniature circuit-breaker/residual current circuit-breaker combination |
Mounting type | Flush-mounted |
number of poles | 2 |
Tripping characteristic | D |
Rated current | 16 A |
Rated current | 0.03 A |
Rated voltage | 230 V |
voltage type | AC |
Insulation voltage (Ui) | 440 V |
Residual current | 0.03 A |
Protection type (IP code) | IP20 |
Country of origin | Romania |
Manufacturer commitment | SBTi |
CO₂ emissions | 18,08 kg |
Climate contribution | EUR 0,44 |
Product Safety |
30-day right of return
Compare products
Goes with
Reviews & Ratings
Statutory warranty score
How often does a product of this brand in the «Residual-current device» category have a defect within the first 24 months?
Source: Galaxus- 1.Brennenstuhl0 %
- 1.Eaton0 %
- 1.Max Hauri0 %
- 1.Schneider Electric0 %
- 5.Siemens0,1 %
Statutory warranty case duration
How many working days on average does it take to process a warranty claim from when it arrives at the service centre until it’s back with the customer?
Source: Galaxus- EatonNot enough data
- 1.Hager0 days
- ABBNot enough data
- BrennenstuhlNot enough data
- Max HauriNot enough data
Return rate
How often is a product of this brand in the «Residual-current device» category returned?
Source: Galaxus- 2.Steffen0,8 %
- 3.Schneider Electric1,5 %
- 4.Eaton2,7 %
- 5.ABB4 %
- 6.Hager4,7 %