Eaton surge arrester SPCT2-385
Manufacturer: Eaton
Designation: Surge arrester insert, 385VAC, 20kA
Type: SPCT2-385
Mains type DC: No
Mains type IT: No
Mains type TN: Yes
Mains type TN-C: No
Mains type TN-C-S: No
Mains type TT: No
Mains type other: Yes
Rated leakage impulse current (8/20): 20 kA
Max. leakage impulse current (8/20): 40 kA
Rated voltage AC: 385 V
Rated voltage DC: 0 V
Max. continuous voltage AC: 385 V
Max. continuous voltage DC: 0 V
Max. PV voltage: 0 V
Protection level: 1.8 kV
Protection level L-N: 0 kV
Protection level N-PE: 0 kV
Max. overcurrent protection Overcurrent protection device Stub wiring (fuse): 0 A
Max. overcurrent protection device V-wiring: 0 V
Overcurrent protection device V-wiring (fuse): 125 A
Short-circuit strength (Isccr): 0 kA
Integrated short-circuit protection: No
Integrated short-circuit protection selective to fuse gG: 0 A
Integrated back-up fuse: No
Leakage current-free: No
Mounting type: On base element
Size: 1 TE
Max. conductor cross-section rigid (one-pole): 0 A
Max. conductor cross-section rigid (solid/multi-stranded): 25 mm²
Max. conductor cross-section flexible (fine-stranded): No
Max. conductor cross-section flexible (flexible): 0 mm²
With remote signalling contact: No
Signalling on the device: Optical
Test class type 2: Yes
Protection class (IP): IP20
Eaton surge arrester SPCT2-385: further details
For protection of consumer installations against transient overvoltages caused by indirect lightning strikes and switching operations, test class II according to IEC 61643-1+A1, SPD-type T2 according to EN 61643-11, auxiliary switch SPC-S-HK can be attached for remote signalling, can be interconnected with all Xtra Combinations switchgear.
Surge protection type | Surge arrester |
Test class | Type 2 |
Item number | 25267290 |
Manufacturer | Eaton |
Category | Surge protection |
Manufacturer no. | 167602 |
Release date | 20.4.2023 |
Minimum order | 2 |
Order quantity steps | 2 |
Surge protection type | Surge arrester |
Lightning impulse current | 40 kA |
Rated leakage surge current | 20 kA |
Nominal voltage | 385 V |
Protection level | 1.80 V |
Test class | Type 2 |
Protection type (IP code) | IP20 |
Country of origin | Romania |
CO₂-Emission | |
Climate contribution |
Width | 1 m |
Product Safety |