ABB Stotz S&J RCD F204A-63/0.03L
Manufacturer: ABB Stotz S&J
Designation: RCD pro M Compact
Type: F204A-63/0.03L
Number of Poles: 4
Rated Voltage: 400 V
Rated Current: 63 A
Rated Residual Current: 0.03 A
Rated Insulation Voltage Ui: 500 V
Rated Impulse Voltage Resistance Uimp: 4 kV
Mounting Type: DIN Rail
Residual Current Type: A
Selective Type: No
Short-Time Delayed Type: No
Short-Circuit Strength (Icw): 1 kA
Surge Current Strength: 0.25 kA
Voltage Type: AC
With Locking Device: Yes
Frequency: Other
Additional Devices Possible: Yes
Protection Class (IP): IP20
Width in Division Units: 4
Installation Depth: 69 mm
Ambient Temperature During Operation: -25..55 °C
Pollution Degree: 2
Connectable Conductor Cross-Section Multi-Wire: 0..25 mm²
Connectable Conductor Cross-Section Single-Wire: 25 mm²
Explosion-Proof: No
ABB Stotz S&J RCD F204A-63/0.03L: Additional Details
Residual Current Devices (RCCBs) provide protection for persons and property as well as protection against electrically ignited fires in accordance with DIN VDE 0100-410 and DIN VDE 0100-530. The F200 series residual current devices ensure protection against sinusoidal alternating currents and pulsating currents with a smooth direct residual current component of up to 6 mA to ground. They also provide fault protection (protection against indirect contact), additional protection (with I?n = 30 mA), and fire protection (with I?n = 300 mA). They comply with product standards IEC/EN 61008-1, 61008-2-1, 61543 (VDE 0664 10, 11, 30) and for F200 A up to 100 A UL 1053. Applications include household, commercial, and industrial uses. The extensive range of accessories provides everything you need for your installation tasks. Numerous approvals make the F200 suitable for worldwide use. F200 A Type A with neutral conductor connection on the left, without UL approval (N conductor on the left required or 3-phase network without N conductor).
Circuit breaker type | Fault current circuit breaker |
Length | 69 mm |
Width | 70 mm |
number of poles | 4 |
Mounting type | Top-hat rail |
Item number | 9893707 |
Manufacturer | ABB |
Category | Residual-current device |
Manufacturer no. | 2CSF204123R1630 |
Release date | 15.10.2018 |
External links |
Colour | Multicoloured |
Exact colour description | Multicoloured |
Circuit breaker type | Fault current circuit breaker |
Mounting type | Top-hat rail |
number of poles | 4 |
Tripping characteristic | A |
Rated current | 63 A |
Rated current | 0.03 A |
Rated voltage | 230 V |
voltage type | AC |
Rated insulation voltage Ui | 500 V |
Residual current (rated differential current) | 0.03 A |
Protection type (IP code) | IP20 |
Country of origin | China |
Manufacturer commitment | SBTi |
CO₂-Emission | |
Climate contribution |
Items per sales unit | 1 Piece |
Length | 69 mm |
Width | 70 mm |
Height | 85 mm |
Weight | 360 g |
Product Safety |
How often does a product of this brand in the «Residual-current device» category have a defect within the first 24 months?
Source: GalaxusHow many working days on average does it take to process a warranty claim from when it arrives at the service centre until it’s back with the customer?
Source: GalaxusUnfortunately, we don't have enough data for this category yet.
How often is a product of this brand in the «Residual-current device» category returned?
Source: Galaxus