Weidmüller Surge arrester s
More than 10 items ordered
Nominal voltage2
Product details
Overvoltage protection. Measurement, control, and regulation without signal function or function display. The following signals fall under the protection of binary signals (SL - Symmetrical Load): switching signals with and without common reference potential of 24V, 5V to 60V. Two-wire systems typically have a common reference potential for binary sensors, actuators, and indicators such as limit switches, pushbuttons, position transmitters, photocells, contactors, solenoid valves, and signal lamps. Pluggable arrester allows for interruption-free and impedance-neutral plugging or unplugging. Testable by the V-TEST device. Space-saving design for up to 4 binary signals. Designed with a ground-free PE connection to avoid interference currents in case of potential differences. Applicable according to installation standards IEC 62305 and IEC 61643-22 (D1, C1, C2, and C3). Integrated PE foot safely dissipates up to 20 kA (8/20 μs) and 2.5 kA (10/350 μs) to PE. Colored marking of voltage levels for quick identification in the control cabinet. Safety function provided by a coding element for different voltage levels.
30-day right of return